Select an indoor load break switch for a 12 kV, 50 Hz circuit, or specify the FKRN12 fuse-combination variant when the circuit needs coordinated fuse protection. The variant, fuse selection and operating mechanism determine the final switching duties.
Select an indoor load break switch for a 12 kV, 50 Hz circuit, or specify the FKRN12 fuse-combination variant when the circuit needs coordinated fuse protection. The variant, fuse selection and operating mechanism determine the final switching duties.
FKN12 is selected for the required indoor load-switching duty. The FKRN12 variant combines the switch with fuses whose rating, characteristic and striker interface form part of the protection arrangement. Specify the operating mechanism, earthing option and auxiliary contacts with the panel design. The approved variant and component schedule define the switching and protection duties.
R identifies fuse protection. The applicable breaking duty depends on the switch variant and fuse combination.
| Electrical parameter | Specification |
|---|---|
| Model options | FKN12-12 switch family; FKRN12-12D fuse-combination family |
| Rated voltage | 12 kV |
| Rated frequency | 50 Hz |
| Active-load breaking current, switch variant | 630 A |
| Closed-loop breaking current, switch variant | 630 A |
| Cable-charging breaking current, switch variant | 10 A |
| Short-time withstand, switch variant | 20 kA for 4 s |
| Fuse-combination short-circuit breaking reference | 31.5 kA; confirm the selected fuse and complete combination |
| Continuous rated current and insulation schedule | Obtain the confirmed variant-specific schedule before selection |
Confirm the selected assembly, component ratings and verification documents. Family options do not describe every supplied configuration.
Match the equipment configuration to the circuit duty and installation interfaces.
| Selection item | Specification / requirement |
|---|---|
| FKN12 load-switch variant | Select for the specified load-switching duty |
| FKRN12 fuse-combination variant | Confirm fuse type, rating, striker and protection coordination |
| Earthing arrangement | Confirm the ordered earthing-switch option and interlocks |
| Operating mechanism | Define manual or other specified operation, shaft and handle interfaces |
| Auxiliary contacts | Define required status signals and secondary wiring |
Confirm the selected order code and component schedule before approval.
Use the selected device only within its confirmed load-switching duties. Do not treat the switch variant as a general fault-interrupting circuit breaker.
For the combination variant, verify the fuse characteristic, transformer or load duty and transfer-current requirements together.
Specify the selected earthing arrangement and interlocking sequence with the panel design.
Confirm operating direction, travel, linkage and auxiliary indication before integration.
Functional overview only. Qualified personnel must follow the approved isolation procedures and supplied operating instructions.
Define the equipment duty and interfaces before requesting the project configuration.
| Configuration item | Purpose | Define for your project |
|---|---|---|
| Switch variant | Perform the specified load-switching duties | Load type, switching current and frequency |
| Fuse-combination variant | Provide coordinated fuse protection | Fuse code, transformer or load data and fault study |
| Earthing and interlocks | Control the approved access sequence | Earthing option and panel scheme |
| Mechanism | Match the panel operating arrangement | Handle, shaft, travel and auxiliary contacts |
| Engineering records | Confirm integration requirements | Variant data sheet and approved drawings |
Final components and scope of supply are defined in the project quotation.
| Interface | Reference / requirement | Selection note |
|---|---|---|
| Panel mounting | Request the selected mounting-hole and support drawing | Match cabinet space and clearances |
| Primary terminals | Confirm phase spacing and terminal geometry | Provide conductor or bus arrangement |
| Operating linkage | Confirm shaft, handle position and travel | Match panel door and operating access |
| Fuse access | Allow the selected fuse arrangement to be serviced | Confirm replacement and isolation procedure |
| Interlocks | Define device-to-door and earthing interfaces | Approve the panel scheme |
Use the approved project drawing for dimensions, clearances, foundations and connections.
Check mounting, phase clearances, terminals, mechanism travel and servicing access against the selected drawing.
Provide the system voltage, frequency, load type, continuous current and available fault level.
Confirm any auxiliary contacts, control voltage and connection diagram for the ordered version.
Request the current variant-specific data sheet, arrangement drawing and applicable test evidence.
| Condition | Requirement / project input |
|---|---|
| Location | Indoor installation |
| Network | 12 kV, 50 Hz selection basis |
| Environment | State temperature, altitude, humidity and contamination |
| Mechanical installation | Provide panel geometry and operating access |
| Nonstandard duty | Confirm capacitive, transformer or other special switching duties |
Provide any conditions outside the stated range before ordering. Final suitability requires project-specific confirmation.
Select the switching duty and coordinate the mechanism, contacts and earthing arrangement with the panel.
For an FKRN12 combination, check the selected fuse characteristics, load duty and transfer-current requirements together.
Planning example: a transformer feeder calls for an FKRN12 switch-fuse combination. The switch, fuse and operating mechanism are selected together.
Provide voltage, load current, transformer duty and the available fault level.
Confirm the fuse rating, time-current characteristic, striker interface and combination duties.
Check the mechanism travel, mounting, earthing option, indication and interlocking sequence.
Production follows the approved drawings, the applicable product standards and the agreed inspection plan.
We can adjust the configuration for your operating environment and provide neutral packaging or your logo. Send the site conditions and branding requirements with your enquiry.
Incoming components, production work and finished units are checked against the requirements for the ordered configuration.
Incoming materials and components are checked against the approved specifications before production.
Assemblies and semi-finished components are inspected at the relevant production stages.
Finished equipment and release records are checked against the approved order requirements.
Factory acceptance testing (FAT). Every unit undergoes FAT before packing. Test items and acceptance criteria follow the product and approved configuration. FAT reports and packing inspection photos accompany the shipment. Factory attendance, video witnessing or independent inspection can be arranged with an agreed scope and schedule.
Send your required ratings, installation conditions and quantity. We will confirm the configuration and documents for your quotation.
Selected FKN12 or FKRN12 assembly and rated duties.
Panel mounting, operating interface and earthing option.
Fuse coordination and applicable assembly verification.
FKN12 is the load-switch family. FKRN12 is the fuse-combination family; its protection duty depends on the selected fuse and complete combination.
Breaking duties and continuous current are separate ratings. Confirm continuous rated current for the selected order code.
Only select a device after checking the required switching and protection duties. The plain switch variant must not be treated as a general short-circuit breaking device.
Confirm the exact variant, earthing option and interlocking arrangement in the equipment schedule.
Send circuit voltage, load type, operating current, fault level, fuse requirements, panel drawing, operating mechanism and auxiliary-signal requirements.