A 40.5 kV outdoor drop-out fuse with a motor-driven operating mechanism. The RRW35-40.5/200-16 combines a 200 A current rating with a listed 16 kA breaking rating. Select the fuse link, drive supply and mounting arrangement for the protected circuit.
A 40.5 kV, 200 A outdoor drop-out fuse with a motor-operated mechanism. Select a 12 V DC or 24 V DC drive and specify the controls for the installation.
The fuse link provides circuit protection. The motor moves the operating mechanism using the selected DC supply. Local or remote controls and position feedback are specified with the controller and wiring.
The structure diagram is a series reference; use the approved outline drawing for mounting and clearances.
Both use a fuse link for protection. The motor-operated fuse adds an electric operating mechanism; the controls and feedback are specified for the order.
On smaller screens, scroll the table sideways to compare both options.
| What to compare | Typical conventional cutout | 40.5 kV motor-operated fuse |
|---|---|---|
| Fault protection | The fuse link melts and interrupts overcurrent within its rated duty. | Fuse-link protection remains. The motor does not replace fuse selection or protection coordination. |
| Routine operation | On-site handling with suitable operating equipment. | Motor operation from a local or remote command, under the approved operating conditions. |
| Status feedback | Visible dropout indication, with on-site checks. | Specify local/remote commands and any position feedback with the controller. |
| Power and controls | No motor supply is needed for the basic fuse assembly. | Select a 12 V DC or 24 V DC motor with compatible control equipment and wiring. |
| After the fuse operates | The operated fuse link must be replaced before returning the circuit to service. | Fuse-link replacement is still required. Motor operation does not reset a blown fuse or make it an automatic recloser. |
| Switching under load | Depends on the cutout design and approved load-break equipment. | Must be confirmed for the selected device. A motor alone does not establish load-break capability. |
A conventional cutout suits installations with on-site operation. Consider the motor-operated fuse when the circuit also needs an electric operating mechanism.
| Electrical parameter | Specification |
|---|---|
| Reference configuration | 40.5 kV / 200 A / 16 kA |
| Rated voltage | 40.5 kV |
| Rated current | 200 A |
| Listed breaking current | 16 kA; confirm applicable duty and test coverage |
| Reference minimum creepage distance | 1255 mm |
| Motor supply | 12 V DC or 24 V DC |
| Device arrangement | Outdoor drop-out fuse with electric operating mechanism |
Match the listed 16 kA breaking rating to the required interruption duty and fuse link. Request the applicable test documents for the selected configuration.
Select the fuse link for the protected load and system fault conditions. Motor operation does not establish load-break capability or an automatic reclosing function. Use the approved replacement link. Follow the supplied isolation and inspection instructions before returning the circuit to service.
| Selection item | Specification / requirement |
|---|---|
| Fuse selection | Specify link rating and protection coordination |
| Drive supply | Select 12 V DC or 24 V DC |
| Control arrangement | Confirm local/remote control and feedback |
| Accessories | Define operating tool, brackets, connectors and controller |
| Insulation requirements | Confirm site pollution and selected insulation schedule |
Select one motor voltage and compatible controls. Specify the control box, commands and feedback with the order.
| Interface | Reference / requirement | Selection note |
|---|---|---|
| Mounting base | Selected arrangement drawing required | Support dimensions and fasteners |
| Fuse movement | Maintain operating clearance | Allow full opening movement |
| Terminals | Confirm conductor interfaces | Material, cross-section and connector detail |
Use the approved support, outline and terminal drawings for installation.
Review the support drawing, phase arrangement, conductor loading and full operating movement. Check the fuse carrier, motor supply, control wiring and specified functions against the approved commissioning instructions.
| Condition | Requirement / project input |
|---|---|
| Installation | Outdoor |
| Reference ambient | -30 to +45 C |
| Reference altitude | 1000 m |
| Reference ice thickness | 2 mm |
| Special exposure | Confirm pollution, corrosion, wind and installation conditions |
State any pollution, corrosion, wind or other site conditions beyond the reference schedule before ordering.
Review the 40.5 kV voltage rating, 200 A current rating and fuse-link duty against the circuit and protected load.
Use the motor-operated mechanism with a selected DC supply. Specify the local/remote controls and feedback required at the site.
Compare the mounting base, conductor interfaces, phase spacing and opening clearance with the proposed 40.5 kV fuse arrangement.
Planning example for selecting a 40.5 kV motor-operated fuse assembly.
HJD catalog arrangement reference. This photograph does not document a 40.5 kV motor-operated fuse installation.
A project needs fuse protection and an electric operating mechanism on an outdoor circuit.
Review the listed 40.5 kV, 200 A and 16 kA ratings against the circuit, fault current and fuse-link duty. Choose a 12 V DC or 24 V DC motor and compatible control equipment. Use the support and conductor drawings to check mounting, phase spacing and opening movement. Define the control-box location, wiring and acceptance checks before installation.
Production follows the approved drawings, the applicable product standards and the agreed inspection plan.
We can adjust the configuration for your operating environment and provide neutral packaging or your logo. Send the site conditions and branding requirements with your enquiry.
Incoming components, production work and finished units are checked against the requirements for the ordered configuration.
Incoming materials and components are checked against the approved specifications before production.
Assemblies and semi-finished components are inspected at the relevant production stages.
Finished equipment and release records are checked against the approved order requirements.
Factory acceptance testing (FAT). Every unit undergoes FAT before packing. Test items and acceptance criteria follow the product and approved configuration. FAT reports and packing inspection photos accompany the shipment. Factory attendance, video witnessing or independent inspection can be arranged with an agreed scope and schedule.
Send the system voltage, quantity, project location and control requirements. Add drawings or site photos if available.
Ratings, mounting dimensions and conductor interfaces.
Selected DC supply, control box, commands and feedback.
Model and duty covered by the available test documents.
Documents are selected for the proposed model and configuration.
For a separate lower-voltage series, review the 24 kV smart fuse configuration.
This is a separate 40.5 kV product rated at 200 A, with a listed 16 kA breaking-current rating. Use its own ratings, dimensions and operating documents.
The applicable interruption duty depends on the selected fuse link and configuration. Review the supporting test documents for the required duty.
This page defines the fuse assembly and motor supply options. Specify any monitoring or communications equipment separately.
No. Select the motor voltage and associated control equipment as one compatible configuration.
Send the system voltage, load and fault currents, quantity, motor supply, control requirements and site conditions. Add the support drawing if available.