An indoor earthing switch for 12 kV switchgear and maintenance earthing arrangements. This design has reference phase pitches of 210, 230, 250 and 275 mm. Match its mounting geometry, operating shaft and interlocks to the switchgear, then confirm the electrical duty for the selected assembly.
An indoor earthing switch for 12 kV switchgear and maintenance earthing arrangements. This design has reference phase pitches of 210, 230, 250 and 275 mm. Match its mounting geometry, operating shaft and interlocks to the switchgear, then confirm the electrical duty for the selected assembly.
JN15-12 provides the earthing-switch component within an indoor switchgear earthing arrangement. The reference design offers several phase pitches, with mounting, shaft and linkage details selected for the panel. Coordinate the switch with the main device, access doors and earth bar. Specify the operating mechanism and any auxiliary contacts in the equipment schedule.
| Electrical parameter | Specification |
|---|---|
| Product family | JN15-12 indoor high-voltage earthing switch |
| System voltage class | 12 kV and below, within the approved application |
| Reference frequency | 50 Hz |
| Application | Earthing arrangement for compatible high-voltage equipment |
| Short-time current and duration | Confirm together on the approved electrical schedule |
| Peak and making duties | Confirm for the selected 12 kV assembly |
| Insulation withstand levels | Obtain the corrected model-specific schedule before selection |
| Operating drive | Specify the required arrangement; motor operation is not assumed |
| Voltage indication | A compatible indication arrangement may be specified separately |
Confirm the selected assembly, component ratings and verification documents. Family options do not describe every supplied configuration.
Specify the drive interface, operating position and interlocks with the switchgear layout. The switch is one component of the complete earthing arrangement.
| Selection item | Define for the ordered assembly |
|---|---|
| Operating drive | Specify manual operation or a separately confirmed motor-drive package; no motor is assumed. |
| Shaft and linkage | Confirm shaft projection, coupling, travel and the side from which the mechanism is operated. |
| Mechanical interlocks | Coordinate the earthing switch with the main switching device, access doors and any withdrawable truck. |
| Position indication | Define local indication and any auxiliary contacts required by the control scheme. |
| Earth connection | Specify the conductor interface and connection to the assembly earth bar. |
A mechanism, motor kit, voltage indicator or auxiliary switch is included only when it appears in the agreed bill of materials.
Use the switch within the approved earthing and interlocking scheme for the equipment being maintained.
An earthing switch is not a substitute for a load-break switch or a circuit breaker. Check the making and withstand duties separately.
Confirm the permitted positions of the earthing switch, main switch and access doors in the project interlock schedule.
Request the operating instructions, interlock verification record and electrical schedule for the delivered assembly.
Functional overview only. Qualified personnel must follow the approved isolation procedures and supplied operating instructions.
Define the equipment duty and interfaces before requesting the project configuration.
| Configuration item | Purpose | Define for your project |
|---|---|---|
| Electrical duty | Select the applicable earthing-switch duty | System voltage, frequency, prospective fault current and required duration |
| Mechanical layout | Match the equipment interfaces | Phase spacing, mounting drawing, shaft location and available clearance |
| Operating mechanism | Define what is delivered | Operating side, drive type, coupling and any confirmed accessories |
| Interlock scheme | Coordinate access and switching positions | Main-device type, truck position if applicable, doors and auxiliary contacts |
| Documentation | Check the selected assembly before manufacture | Approved drawing, nameplate schedule, inspection records and operating instructions |
Final components and scope of supply are defined in the project quotation.
| Reference variant | L overall length (mm) | E phase pitch (mm) | C dimension (mm) |
|---|---|---|---|
| JN15-12/31.5-210 | 655 | 210 | 516 |
| JN15-12/31.5-230 | 710 | 230 | 556 |
| JN15-12/31.5-250 | 760 | 250 | 596 |
| JN15-12/31.5-275 | 810 | 275 | 646 |
Reference mechanical variants only. The /31.5 marking in a dimension code does not by itself confirm the complete withstand duty or duration. Dimensions are in mm; use the approved drawing.
Check the selected phase spacing, hole pattern, mechanism envelope and shaft position against the approved assembly drawing.
Coordinate the switch, busbars, cables and enclosure using the required insulation clearances for the selected voltage class.
Confirm the connection size, termination details and assembly instructions with the switchgear design.
Allow access for the specified inspection and maintenance work without relying on the reference image as an installation drawing.
| Condition | Requirement / project input |
|---|---|
| Location | Indoor, within the selected equipment arrangement |
| Reference altitude | Up to 1000 m; confirm higher-altitude applications |
| Ambient temperature | Specify the site minimum and maximum for written confirmation |
| Contamination and condensation | Define exposure and the enclosing equipment conditions |
| Vibration and seismic duty | Provide the project requirement for verification |
Provide any conditions outside the stated range before ordering. Final suitability requires project-specific confirmation.
Match the switch and its earth connection to the panel layout and approved interlock scheme.
Use the installed mounting pattern, phase pitch, operating shaft and contact positions to select the replacement.
Planning example: a panel needs a replacement JN15-12 assembly. Matching the model prefix is only the starting point for the review.
Provide the installed switch nameplate, phase pitch, mounting dimensions and operating-side arrangement.
Request the corrected schedule for the selected unit, including insulation, making and withstand duties.
Match the shaft, linkage and auxiliary contacts to the panel interlock and earthing scheme.
Production follows the approved drawings, the applicable product standards and the agreed inspection plan.
We can adjust the configuration for your operating environment and provide neutral packaging or your logo. Send the site conditions and branding requirements with your enquiry.
Incoming components, production work and finished units are checked against the requirements for the ordered configuration.
Incoming materials and components are checked against the approved specifications before production.
Assemblies and semi-finished components are inspected at the relevant production stages.
Finished equipment and release records are checked against the approved order requirements.
Factory acceptance testing (FAT). Every unit undergoes FAT before packing. Test items and acceptance criteria follow the product and approved configuration. FAT reports and packing inspection photos accompany the shipment. Factory attendance, video witnessing or independent inspection can be arranged with an agreed scope and schedule.
Send your required ratings, installation conditions and quantity. We will confirm the configuration and documents for your quotation.
Insulation, making and withstand duties for the selected unit.
Phase pitch, fixing points, shaft and linkage.
Operating instructions and applicable verification.
No. Match the mounting pattern, phase pitch, shaft and clearances. A shared model prefix does not establish a drop-in replacement.
The reference drawing lists E = 210, 230, 250 and 275 mm. Their overall lengths and C dimensions are shown in the table.
The short-circuit and insulation ratings are not yet confirmed for the selected assembly. Request the approved model-specific electrical schedule before selection.
Neither is assumed. Specify the operating arrangement and any compatible indication or auxiliary-contact package in the order.
Provide the existing nameplate, mounting drawing, phase pitch, operating-shaft details, interlock arrangement and required electrical duty.