What Is Low Voltage Switchgear? Components and Specification Basics

Learn what low voltage switchgear includes, how breaker and assembly ratings differ, and what to specify before requesting a project quotation.

Low voltage switchgear controls, protects and isolates low-voltage electrical circuits.[1] When buying an assembled board, you need to specify the complete system: switching devices, busbars, internal connections, controls and enclosure.[4] A circuit-breaker datasheet covers only part of that purchase.

Start with the supply voltage, load requirements and prospective short-circuit current at the installation point. Then check whether the proposed assembly, its devices and its installation conditions match those inputs. A breaker marked with a high kA value does not, by itself, establish the short-circuit capability of the complete board.[5][6][8]

What counts as low voltage?

For power switchgear and controlgear assemblies within IEC 61439-2:2020, the published scope covers rated voltages up to 1,000 V AC or 1,500 V DC.[2] Those are scope limits, not operating ratings for every product described as low voltage switchgear.

State the actual voltage, AC or DC supply and frequency in the enquiry. Check the declared operating voltage of each device rather than assuming that a familiar enclosure or model name establishes suitability.[6][8]

On an IEC-based project, identify the applicable assembly standard and edition. IEC 61439-1 gives general rules; conformity assessment also uses the relevant subsequent part, such as IEC 61439-2 for power switchgear and controlgear assemblies.[3] Ask the supplier to identify that basis in the quotation.

What is inside a complete assembly?

An incoming circuit receives the supply, a busbar system distributes it, and outgoing circuits feed individual loads or downstream distribution equipment.[4] The functional groups below help define the supply boundary.

  • Incoming and outgoing switching or protective devices perform the circuit duties assigned to them.[1][4]
  • Busbars, internal conductors and terminals connect those devices to each other and to external circuits.[4]
  • Metering and control equipment provide the specified measurement, indication and control functions.[1]
  • The enclosure and structural parts belong within the assembly specification.[3]

The complete assembly includes the devices, busbars, internal connections and supporting enclosure.[3][4]

An incoming device feeds a busbar and three outgoing devices inside the assembly boundary, alongside a metering and control group.

Ask for a single-line diagram and a general arrangement drawing alongside the component list. Use them to check what the supplier includes, where cables terminate and which functions need separate equipment. A list of breaker brands cannot answer those layout questions.

Is low voltage switchgear the same as a switchboard?

The terms can overlap in IEC-oriented distribution discussions. Schneider Electric describes distribution switchboards as assemblies of functional units and relates their construction to IEC 61439.[4] That makes the product label alone a weak basis for comparing offers.

For a tender, compare the stated assembly standard, construction, device arrangement and declared ratings. If two suppliers use different names, ask them to map their offers against the same specification.

Read current and short-circuit ratings separately

Continuous current describes a different duty from interrupting a fault.[6][10] Record the quantity, the equipment it belongs to and its conditions in separate quotation fields.

Normal loading

The assembly’s declared current applies to its particular arrangement and temperature-rise limits.[10] A large incoming breaker frame does not establish how much current the complete board can carry under the project’s conditions.[10]

Provide the load schedule and identify circuits expected to operate together. Ambient temperature, the enclosure and the application affect device selection; avoid applying a single generic derating percentage to every configuration.[8] Ask the supplier to state the loading and cooling assumptions behind the offered assembly rating.

Breaker breaking capacity: Icu and Ics

For industrial circuit-breakers under IEC 60947-2, Icu is the rated ultimate short-circuit breaking capacity. It concerns the device’s interruption duty under the applicable test conditions.[6] Ics is the rated service short-circuit breaking capacity, associated with a test sequence and subsequent service-performance checks.[7]

Read both at the relevant operating voltage. Keep the exact breaker model and trip unit in the technical schedule.[6][8] An Ics value is not permission to re-energize damaged equipment after a real fault; fault investigation and the manufacturer’s inspection requirements remain necessary.

Assembly withstand: Icw and Ipk

For an assembly, Icw is a short-time withstand current expressed as an RMS current with a specified duration. Ipk is the peak short-circuit current the assembly is declared to withstand under specified conditions.[5]

Read breaker breaking capacity and assembly withstand as separate requirements, even when both are expressed in kA.[5][6]

Two cards separate breaker Icu and Ics breaking capacity from assembly Icw, Ipk and conditional Icc ratings.

Also check which equipment owns a rating: certain circuit-breakers have their own Icw, which does not automatically establish the assembly’s Icw.[7] If an assembly is offered with conditional short-circuit current Icc, obtain the specified protective-device combination and conditions on which that declaration depends.[5]

Selectivity and back-up protection need separate attention. Use the manufacturer’s applicable coordination data for the exact device combination and voltage; a larger upstream breaker or a familiar brand name does not establish coordination.[9]

A specification-reading example

Consider a hypothetical enquiry for a 400 V AC board with a calculated prospective short-circuit current of 50 kA at its incoming terminals. These are example project inputs, not HJD product ratings.

A reply stating only “50 kA breaker” leaves several questions open:

  • Is that the breaker’s Icu or Ics, and at which voltage?
  • What assembly short-circuit rating is offered, and with which duration or protective-device conditions?
  • Does the proposed protection arrangement satisfy the project’s fault-clearing and coordination requirements?

Ask for the missing declarations before accepting the offer as equivalent. Do not invent a required Icw duration from the fault-current magnitude alone. The project designer must establish the required fault duty and protection arrangement; the supplier must show how the offered configuration meets them.[5][8][9]

Check installation and maintenance assumptions

A board can have suitable electrical ratings and still be poorly specified for its location. Give the supplier the ambient conditions and installation environment, then confirm the enclosure and cooling arrangement used for the offered ratings.[2][8]

Use the layout review to settle cable entry, termination space, access sides and the available room envelope. Mark obstructions on the drawing instead of asking only whether the cabinet “fits.” Include the required maintenance access and the route for bringing equipment into the room.

Fixed, disconnectable and withdrawable functional units are different construction arrangements.[4] Choose against the project’s maintenance plan and permitted shutdowns. Ask what must be isolated before removal or servicing; a withdrawable arrangement does not itself authorize live work.

Request evidence covering the offered assembly design and a routine-verification record for the manufactured board. Design verification addresses the design; routine verification checks each manufactured assembly.[4] Component certificates alone do not establish the complete assembly’s conformity.[3]

What to send with a low voltage switchgear enquiry

Use the following checklist to turn an initial product enquiry into a configuration the supplier can review.

Information to sendWhat the quotation should resolve
Supply systemActual voltage, AC or DC, frequency, earthing arrangement and source details.
Single-line diagram and load scheduleIncoming circuits, outgoing duties, simultaneous loading and planned additions.
Fault-study inputsProspective fault current at the board and the required assembly short-circuit duty.
Protection requirementsDevice models, trip units, coordination basis and any back-up protection conditions.
Environment and room layoutAmbient conditions, enclosure needs, access, cable entry and termination space.
Maintenance requirementsFunctional-unit arrangement, permitted outages and required isolation provisions.
Standards and acceptance documentsApplicable editions, declared ratings, drawings, design-verification evidence and routine-verification records.

If the board is transformer-fed, collect the transformer information alongside the LV enquiry. The transformer specification checklist provides a starting point for organizing those inputs; the project’s fault study must establish the fault level at the board.

For an HJD enquiry, send the single-line diagram and the available checklist inputs. Ask HJD to confirm the proposed supply boundary, declared ratings, supporting documents and any unresolved items in writing. This gives you a defined offer to assess before procurement.

Questions about low voltage switchgear

A breaker rating does not establish the board’s capability.[5][6] Ask for the assembly declaration. Where the proposal relies on a protective device limiting fault stress, obtain the stated combination and conditions supporting that arrangement.[5]

No. IEC states that the relevant part from Part 2 onward applies together with the cited requirements of Part 1.[3] Ask which product-specific part and edition apply, then request evidence for the offered configuration.

Only when the complete configuration and its devices are declared suitable for the required DC duty. AC and DC characteristics belong in device selection; an AC operating-voltage marking does not establish DC suitability.[6][8]

An empty position establishes available space. Confirm the future load against the assembly’s current rating, simultaneous loading and temperature-rise verification before treating it as electrical capacity.[3][10] Include the expected future duty in the original enquiry when it is known.

Sources

  1. G&W Electric: Switchgear Fundamentals, Types and Key Components
  2. IEC 61439-2:2020: Power switchgear and controlgear assemblies
  3. IEC 61439-1:2020: General rules
  4. Schneider Electric: Distribution switchboards
  5. ABB: Low Voltage Switchgear and IEC 61439, slides 8 and 26
  6. Schneider Electric: Fundamental characteristics of a circuit-breaker
  7. Schneider Electric: Other characteristics of a circuit-breaker
  8. Schneider Electric: Selection of a circuit-breaker
  9. Schneider Electric: Coordination between circuit-breakers
  10. Schneider Electric: Rated current of electrical panel and switchboard protection devices
HJD Electrical
HJD Electrical

I focus not only on the product itself, but also on the manufacturing realities behind it. My articles are based on actual customer projects, product development, and factory experience. I share real manufacturing challenges, cost considerations, and workable solutions to help readers make better decisions.

Need a Project Quote? Let’s Build It Together.

Send your product list, technical ratings, quantity and delivery destination.
The HJD team will review your requirements and respond within 24 hours.